Schneider Electric Easy UPS 3S – Technical Specifications
Power Ratings
-
Models: 10, 15, 20, 30, 40 kVA (kW = kVA)
-
Phase Options:
-
3:1 – 10/15/20/30 kVA
-
3:3 – 10/15/20/30/40 kVA
-
Input
-
Voltage: 380/400/415 V (3-phase + Neutral)
-
Frequency: 45–65 Hz
-
Power Factor: >0.99
-
THDi:
-
<3% (10 kVA)
-
<4% (15–40 kVA)
-
-
Voltage Range: 304 – 477 V at full load
-
Dual mains input: Yes (default single mains input)
Output
-
Voltage:
-
3:1 – 220/230/240 V
-
3:3 – 380/400/415 V
-
-
Efficiency:
-
Double conversion: up to 96%
-
ECO mode: up to 99%
-
-
Overload Capacity:
-
130% for 10 min
-
130–150% for 1 min
-
-
Voltage Tolerance: ±1%
Battery
-
Type: VRLA (Valve-Regulated Lead Acid)
-
Nominal DC Bus: ±192 to ±240 V
-
Charging Power: Selectable, 1–20% of output power
Communication & Control
-
Interfaces: RS485, Dry contacts, Ethernet (SNMP, Modbus TCP/IP, BACnet)
-
Control Panel: Multi-function LCD, status & display console
Mechanical & Physical
-
External Battery Models (H × W × D mm / weight kg):
-
10–15 kVA: 530 × 250 × 700 mm / 36–50 kg
-
20–30 kVA: 770 × 250 × 800 mm / 58–77 kg
-
40 kVA: 770 × 250 × 900 mm / 70–86 kg
-
-
Internal Battery Models (H × W × D mm / weight kg without batteries):
-
10–20 kVA: 1400 × 380 × 928 mm / 112–158 kg
-
30–40 kVA: 1400 × 500 × 969 mm / 152–195 kg
-
-
Battery Module: 27–28 kg per module
Environmental
-
Operating Temp: 0°C to 40°C
-
Humidity: 0–95% non-condensing
-
Elevation: 0–1000 m at 100% load
-
Audible Noise:
-
10–20 kVA: 60 dBA
-
30–40 kVA: 63 dBA
-
-
Protection Class: IP20
Regulatory Compliance
-
Safety: IEC/EN 62040-1
-
EMC/EMI/RFI: IEC 62040-2
-
Performance: IEC 62040-3
-
Environmental: IEC 62040-4
-
Markings: CE, RCM, EAC, WEEE