Galaxy VS UPS Technical Specifications
| Category | Specification |
|---|---|
| Topology | On-line double conversion |
| Nominal Power (kW) | 10 – 150 kW (parallel up to 600 kW, 4 UPSs in parallel) |
| Key Features | Scalability: 50 – 150 kW N+1 redundancy: 20 – 50 kW N+1 Modular elements: Power modules with Live Swap, static switch module, smart battery modules, intelligence module Display: 4.3″ color touchscreen, status LED, mimic on display |
| Network/Control | Network Management Card included (Ethernet SNMP & Modbus), 8 dry contacts (4 inputs, 4 outputs) |
| Maintenance Bypass | Internal maintenance bypass; optional maintenance bypass panel |
| Parallel Capability | Simplified 1+1 parallel (redundancy); up to 4 UPSs in parallel (capacity or redundancy) |
| Efficiency | Double Conversion Mode: Up to 97% Eco Mode: Up to 99% ECOnversion Mode: Up to 99% |
| Input | Voltage: 380 / 400 / 415 V Range: ±15% (phase-to-phase) Frequency: 40 – 70 Hz Power Factor: >0.99 (load >25%), >0.95 (load >15%) Single/dual mains supported Max short-circuit rating: 65 kA Backfeed protection: Included |
| Output | Voltage: 380 / 400 / 415 V Load PF: 1 (0.7 leading to 0.7 lagging without derating) Voltage Regulation: ±1% Frequency: 50/60 Hz ±0.1% (free running) Overload: 150% (1 min), 125% (10 min) THDU: <1% (linear load) |
| Battery | Types: VRLA, Lithium-ion Nominal Voltage (external batteries): 480–576 V (50, 100, 150 kW); 432–576 V (60 kW); 384–576 V (other ratings incl. 60 & 120 kW) Nominal Voltage (internal batteries): 480 VDC Charging Power: 80% (0–40% load), 20% (100% load) |
| Environment | Acoustic Noise (external battery models): 57 dB (70% load) / 65 dB (100% load) Acoustic Noise (internal battery models): 54–65 dB (depending on load/model) Dust protection: Air filter included; conformal coated boards Seismic: With optional kit (OSHPD tested) Environmental: RoHS, REACH |
| Certifications | EMC Level C2, Seismic certified (optional kit), Marine certifications (DNV, BV) available |


Reviews